Defect 1. Location
Area/Floor/Level
Defect 1. Notes
Defect 1.
Existing lighting cabling is currently not supported off the ceiling grid, this is non compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 1. Photos
Take Photo/s
Cancel
of
Add another item?
Yes
No
Back
Next
Save
Defect 2. Location
Area/Floor/Level
Defect 2. Notes
Defect 2.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 2. Photos
Take Photo/s
Cancel
of
Add another item?
Yes
No
Back
Next
Save
Defect 3. Location
Area/Floor/Level
Defect 3. Notes
Defect 3.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 3. Photos
Take Photo/s
Take as many as you like
Cancel
of
Add another item?
Yes
No
Back
Next
Save
Defect 4. Location
Area/Floor/Level
Defect 4. Notes
Defect 4.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 4. Photos
Take Photo/s
Cancel
of
Add another item?
Yes
No
Back
Next
Save
Defect 5. Location
Area/Floor/Level
Defect 5. Notes
Defect 5.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 5. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 6. Location
Area/Floor/Level
Defect 6. Notes
Defect 6.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 6. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 7. Location
Area/Floor/Level
Defect 7. Notes
Defect 7.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 7. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 8. Location
Area/Floor/Level
Defect 8. Notes
Defect 8.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 8. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 9. Location
Area/Floor/Level
Defect 9. Notes
Defect 9.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 9. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 10. Location
Area/Floor/Level
Defect 10. Notes
Defect 10.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 10. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 11. Location
Area/Floor/Level
Defect 11. Notes
Defect 11.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 11. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 12. Location
Area/Floor/Level
Defect 12. Notes
Defect 12.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 12. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 13. Location
Area/Floor/Level
Defect 13. Notes
Defect 13.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 13. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 14. Location
Area/Floor/Level
Defect 14. Notes
Defect 14.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 14. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 15. Location
Area/Floor/Level
Defect 15. Notes
Defect 15.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 15. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 16. Location
Area/Floor/Level
Defect 16. Notes
Defect 16.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 16. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 17. Location
Area/Floor/Level
Defect 17. Notes
Defect 17.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 17. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 18. Location
Area/Floor/Level
Defect 18. Notes
Defect 18.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 18. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 19. Location
Area/Floor/Level
Defect 19. Notes
Defect 19.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.
Other
Defect 19. Photos
Take Photo/s
Cancel
of
Add another?
Yes
No
Back
Next
Save
Defect 20. Location
Area/Floor/Level
Defect 20. Notes
Defect 20.
Existing lighting cabling is currently not supported off the ceiling grid, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (c)
Where sheathed cables pass through metallic parts of any building structure it is required the opening be bushed to eliminate the hazard of it being damaged on the metallic building material. AS3000:2018 -clause 3.9.3.1
Exposed copper not enclosed by an insulator; this is non-compliant as per AS3000:2018 – clause 1.5.11.4
Damage found to existing wiring inside the metal ducted skirting.
Single insulation exposed; this is non-compliant. Double insulation must be maintained when not enclosed by a form of mechanical protection.
Existing light fixtures with blown globes.
Existing mechanical control boxes are open exposing potential 415v terminals.
Existing cabling resting on a metal fire service, this is non-compliant as per AS3000:2018 – Clause 3.9.3.2 (c)
Existing lighting cabling is currently tied to ceiling grid hangers, this is non complaint as per AS3000:2018 – Clause 3.9.3.2 (b)
There is no segregation between LV and ELV (power and data) required by ASNZ3000:2018 - Clause 3.9.8.4 figure 8. 50mm minimum separation or barrier of durable insulating material.
50mm minimum separation or barrier of durable insulating material.
Existing Ducted Skirting has multiple holes in the skirting lid throughout the tenancy.
Exposed copper outside of C-Bus terminal.