You can always press Enter⏎ to continue
Fire Alarm Yearly Monthly Routine Maintenance
START
1
Person completing the testing
First Name
Last Name
Previous
Next
Submit
Press
Enter
2
Site
Previous
Next
Submit
Press
Enter
3
Date
-
Date
Year
Month
Day
Previous
Next
Submit
Press
Enter
4
Testing to be completed on this visit
Monthly
6 Monthly
Yearly
5 Yearly
Fire Alarm
Yes
No
N/A
Yes
No
N/A
Row 0, Column 0
Yes
No
N/A
Yes
No
N/A
Row 0, Column 1
Yes
No
N/A
Yes
No
N/A
Row 0, Column 2
Yes
No
N/A
Yes
No
N/A
Row 0, Column 3
Fire Extinguishers
Yes
No
N/A
Yes
No
N/A
Row 1, Column 0
Yes
No
N/A
Yes
No
N/A
Row 1, Column 1
Yes
No
N/A
Yes
No
N/A
Row 1, Column 2
Yes
No
N/A
Yes
No
N/A
Row 1, Column 3
Fire Sprinklers
Yes
No
N/A
Yes
No
N/A
Row 2, Column 0
Yes
No
N/A
Yes
No
N/A
Row 2, Column 1
Yes
No
N/A
Yes
No
N/A
Row 2, Column 2
Yes
No
N/A
Yes
No
N/A
Row 2, Column 3
Hydrants
Yes
No
N/A
Yes
No
N/A
Row 3, Column 0
Yes
No
N/A
Yes
No
N/A
Row 3, Column 1
Yes
No
N/A
Yes
No
N/A
Row 3, Column 2
Yes
No
N/A
Yes
No
N/A
Row 3, Column 3
Pumps
Yes
No
N/A
Yes
No
N/A
Row 4, Column 0
Yes
No
N/A
Yes
No
N/A
Row 4, Column 1
Yes
No
N/A
Yes
No
N/A
Row 4, Column 2
Yes
No
N/A
Yes
No
N/A
Row 4, Column 3
Fire Hose Reels
Yes
No
N/A
Yes
No
N/A
Row 5, Column 0
Yes
No
N/A
Yes
No
N/A
Row 5, Column 1
Yes
No
N/A
Yes
No
N/A
Row 5, Column 2
Yes
No
N/A
Yes
No
N/A
Row 5, Column 3
Gas System
Yes
No
N/A
Yes
No
N/A
Row 6, Column 0
Yes
No
N/A
Yes
No
N/A
Row 6, Column 1
Yes
No
N/A
Yes
No
N/A
Row 6, Column 2
Yes
No
N/A
Yes
No
N/A
Row 6, Column 3
Fire Alarm
Fire Extinguishers
Fire Sprinklers
Hydrants
Pumps
Fire Hose Reels
Gas System
Monthly
Yes
No
N/A
Yes
No
N/A
Row 0, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 0, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 0, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 0, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 1, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 1, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 1, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 1, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 2, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 2, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 2, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 2, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 3, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 3, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 3, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 3, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 4, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 4, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 4, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 4, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 5, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 5, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 5, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 5, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 6, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 6, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 6, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 6, Column 3
1
of 7
Previous
Next
Submit
Press
Enter
5
3.1 Monthly/6 Monthly service completed
COMPLETE all monthly and six-monthly service activities, as listed in Table 6.4.1.2 and 6.4.1.3.
Previous
Next
Submit
Press
Enter
6
3.2 Manual call points
CHECK all manual call points are free of conditions likely to adversely affect their function. TEST the operation of each manual call point.
Previous
Next
Submit
Press
Enter
7
3.3 Other warning devices
Where other warning devices are used as the alarm-indicating devices, INSPECT all devices to ensure that they are in place.
Previous
Next
Submit
Press
Enter
8
3.4 Panel switches and keypad
TEST the operation of each control.
Previous
Next
Submit
Press
Enter
9
3.5 Visual indicators
TEST the operation of each visual indicator and alphanumeric displays.
Previous
Next
Submit
Press
Enter
10
3.6 Battery
MEASURE system quiescent and maximum alarm currents in accordance with Appendix F. Calculate the required battery capacity and CHECK the nominal capacity of the installed batteries is not less than the calculated capacity. Verify that the measured currents are the same as recorded in the baseline data. Record the readings in the comments section
Previous
Next
Submit
Press
Enter
11
3.7 Fire Detectors
TEST detectors as specified in Appendix G and confirm correct alarm zone indication. Where the detectors are used as part of special hazards systems 100% of the detectors shall be functionally tested yearly.
Previous
Next
Submit
Press
Enter
12
3.8 Audibility
TEST the occupant warning system and check the signals are distinctly audible in all areas of the building. NOTE: In order to reduce the disturbance to occupants an acceptable means of conducting this test is to provide an audio signal other than the warning signal at a reduced sound pressure level. Where the FIP is connected to a sound systems and intercom systems for emergency purposes (AS 1670.4) or EWIS (AS 2220.2) test in accordance with Table 6.4.3.2.
Previous
Next
Submit
Press
Enter
13
3.9 Occupant warning sound levels
MEASURE and record the sound pressure level from at least one reference point for each amplifier used and ensure at each reference point the measured value is consistent with the baseline sound pressure level at each reference point (see AS 1670.1). Record the levels in the comments section
Previous
Next
Submit
Press
Enter
14
3.10 Alarm acknowledge facility
TEST not less than 20% of installed alarm acknowledgement facilities in such a manner that over a 5-year period, all facilities are tested. CHECK the alarm acknowledgement facility functions in accordance with the approved design.
Previous
Next
Submit
Press
Enter
15
3.11 Alarm investigate facility
TEST the alarm investigation facility if enabled and check it functions in accordance with the approved design.
Previous
Next
Submit
Press
Enter
16
3.12 Batteries condition
When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.
Previous
Next
Submit
Press
Enter
17
3.13 Smoke and heat alarms
Refer to Clause 6.4.2.
Previous
Next
Submit
Press
Enter
18
3.14 Service life
Inspect detectors, equipment or other items having a defined service life and report where the service life is exceeded or will be exceeded before the next scheduled service.
Previous
Next
Submit
Press
Enter
19
3.15 Baseline data
CONFIRM the baseline data is accurate.
Previous
Next
Submit
Press
Enter
20
3.16 Protected areas survey
SURVEY all areas of the building from floor level and check— (a) that the fire detection and alarm system has not been altered from the approve design, damaged or compromised; (b) detection device and remote indicators are appropriate for the current use; (c) for any condition that may cause a nuisance alarm or the unintentional operation of a suppression system; (d) all exposed cabling, conduits, junction boxes and the like for any condition that may impact on the performance of the system and is labelled in accordance with approved design; and (e) all CIE to ensure all components are appropriately mounted and secure.
Previous
Next
Submit
Press
Enter
21
3.17 Interfaced system initiation
Simulate alarm(s) to verify that each interface transmission path initiates the corresponding interfaced system(s) in accordance with the approved design.
Previous
Next
Submit
Press
Enter
22
3.18 FFCP latching and reset
Previous
Next
Submit
Press
Enter
23
3.19 Manual override controls
CHECK that manual override ON-AUTO-OFF control operates. NOTE: Manual override should function in normal mode and fire mode.
Previous
Next
Submit
Press
Enter
24
3.20 Airflow fault indicator
CHECK the operation of the airflow fault indicator
Previous
Next
Submit
Press
Enter
25
3.21 Open-circuit fault indicator
CHECK the operation of the air-handling equipment interconnecting cable open-circuit fault indicator.
Previous
Next
Submit
Press
Enter
26
3.22 Closed-circuit fault indicator
CHECK the operation of the air-handling equipment interconnecting cable closed-circuit fault indicator.
Previous
Next
Submit
Press
Enter
27
3.23 Electrical
CHECK the operation of the electricity phase fail fault indicator.
Previous
Next
Submit
Press
Enter
28
3.24 Fan-running indicator
CHECK the operation of the fan-running indicator.
Previous
Next
Submit
Press
Enter
29
3.25 Fan-stopped indicator
CHECK the operation of the fan-stopped indicator.
Previous
Next
Submit
Press
Enter
30
3.26 Fan fault indicator
CHECK the operation of the fan-fault indicator.
Previous
Next
Submit
Press
Enter
31
3.27 Status monitoring
TEST the each suppression system status monitored function (e.g. container level, pressure switches, pump controllers, isolation valves) and CHECK each monitored function indicates at the suppression system control panel.
Previous
Next
Submit
Press
Enter
32
3.28 Suppression system directional valves
SIMULATE the system operation and confirm that each electrical directional valve operates according to the approved design.
Previous
Next
Submit
Press
Enter
33
3.29 Discharge time and delay
TEST and RECORD the system discharge sequence and confirm the time delay period is in accordance with the approved design.
Previous
Next
Submit
Press
Enter
34
3.30 Agent release indication
TEST the agent release detection device (e.g. pressure switch) and confirm the operation of the agent release is indicated at the FIP.
Previous
Next
Submit
Press
Enter
35
Test Results of devices
Previous
Next
Submit
Press
Enter
36
Testing comments/Suggestions/Defects
Huge
Large
Normal
Small
Ok
quote
Created with Sketch.
Ok
Previous
Next
Submit
Press
Enter
37
Testing comments/Suggestions/Defects Photos
Drag and drop files here
Select files to upload
Max. file size
: 10.6MB
Browse Files
Cancel
of
Previous
Next
Submit
Press
Enter
38
Signature
Clear
Previous
Next
Submit
Press
Enter
Should be Empty:
Question Label
1
of
38
See All
Go Back
Submit