    Complete all monthly service activities, as listed in Table 6.4.1.2.
    Press
    Enter
  • 6
    a) Ensure that they are clearly visible readily accessible and free from dust and contaminants. (b) Check that the door is correctly labelled.
    Press
    Enter
  • 7
    INSPECT all visual warning devices, including: • DO NOT ENTER • EVACUATE • FIRE ALARM • SYSTEM INOPERATIVE for any condition or damage that is likely to adversely affect their function.
    Press
    Enter
  • 8
    TEST the operation of each inhibit or auto/manual switch and confirm that: (a) It prevents the automatic discharge of suppression system. (b) Stops and resets the normal system discharge sequence. (c) Causes the illumination of a visual indicator at the LCS and the system FIP. (d) Causes an audible indication. (e) Does not override the operation of the manual discharge switch.
    Press
    Enter
  • 9
    TEST the operation of the manual initiate switch and confirm normal system discharge sequence, including fire and evacuation alarms, time delays equipment shutdowns, and that it overrides the LCS discharge inhibit switch.
    Press
    Enter
  • 10
    CONFIRM the system inoperative VWD operates for: (a) Operation of a service switch (discharge initiating circuit electrical isolation). (b) Fault in the discharge actuator circuit. (c) Operation of a lock-off valve (where fitted). (d) Operation of a manual inhibit switch (where fitted). (e) Isolation or fault in any part of the fire detection or control system that prevents the automatic or electrical manual discharge of the suppression system.
    Press
    Enter
  • 11
    TEST the system logic (e.g. dual detector operation or dependency on more than one alarm) and confirm that the operation of • VWDs • audible alarms • directional valve signal/output • equipment fire mode signal/output • HVAC fire mode signal/output • system discharge actuator • door and damper release and • ancillary controls is in accordance with the approved design.
    Press
    Enter
  • 12
    TEST each supervised actuator circuit to ensure a fault is registered at the FIP.
    Press
    Enter
  • 13
    TEST the function of each actuator and ensure that each actuator operates correctly. Ensure that each actuator has been mechanically isolated or temporarily removed from the suppressant supply to prevent unintended discharge. For non-resettable actuators (e.g. pyrotechnic types) substitute the actuator with a load of equivalent value and CONFIRM the operating current is in accordance with baseline data.
    Press
    Enter
  • 14
    Press
    Enter
  • 15
    • Huge
    • Large
    • Normal
    • Small
    Ok