  • Marking the units with the next test date (Month-Year):
    Gloves - 6 months unless shorter time period indicated here: .

    Sleeves - 12 months unless shorter time period indicated here: .

    Blankets - 12 months unless shorter time period indicated here: .

  • All processing will be in accordance with ASTM F479 & F496 procesures, including:

    1. Check-in and quantity verification.
    2. Cleaning and removing old marks.
    3. Visual inspection of inner and outer surface of gloves & sleeves, both surfaces for blankets.
    4. Dielectric test at the rated proof test voltage for 1 minute.
    5. Prepare for return shipment including failed products (with failures noted). Be sure to pack your products properly. Over-stacking and pressing cal put stress on the products and lead to premature failure.