Fire Hydrant Monthly Routine Maintenance

Fire Hydrant Monthly Routine Maintenance

  • 1
    Press
    Enter
  • 2
    Press
    Enter
  • 3
    -
    Pick a Date
    Press
    Enter
  • 4
    1 of 7
    Press
    Enter
  • 5
    Where pumpsets are fitted complete all pumpset monthly service activities, as listed in Table 3.4.1.
    Press
    Enter
  • 6
    (a) CHECK that all isolating valves to pump starting pressure devices are secured in the open position. (b) CHECK that pressure switches are securely mounted and are protected against the ingress of water, dust and insects.
    Press
    Enter
  • 7
    (a) START each pumpset by reducing the applied water pressure to the pump-starting device and run engine, in accordance with Section 3. (b) RESTART the pumpset using the manual starting device and again run the compression ignition engine in accordance with Section 3. Where more than one starting device is installed, including the manual starting device, the test may be carried out on a rotating basis. The period between the exercising of each starting device is not to exceed 3 months. Where this would require the pump to start more than 5 times in succession, the period may be extended to 6 months (see also Table 3.4.3, Items 3.6 and 3.7). (c) RECORD the pump cut-in pressures and verify that they are within the ranges indicated on the pressure gauge schedule. ………kPa ………kPa
    Press
    Enter
  • 8
    (b) RESTART the pumpset using the manual starting device and again run the motor in accordance with Section 3. (c) Where more than one starting device is installed, including the manual starting device, the test may be carried out on a rotating basis. The period between the exercising of each starting device is not to exceed 3 months. Where this would require the pump to start more than 5 times in succession, the period may be extended to 6 months. ………..kPa ………. kPa
    Press
    Enter
  • 9
    After completion of testing procedures, RETURN all equipment to the operational condition.
    Press
    Enter
  • 10
    Press
    Enter
  • 11
    • Huge
    • Large
    • Normal
    • Small
    Ok
    quoteCreated with Sketch.
    Ok
    Press
    Enter
  • 12
    Drag and drop files here
    Select files to upload
    Max. file size: 10.6MB
    Cancelof
    Press
    Enter
  • 13
    Clear
    Press
    Enter
  • Should be Empty:
Question Label
1 of 13See AllGo Back
close