You can always press Enter⏎ to continue
Fire Hydrant Yearly Routine Maintenance
START
1
Person completing the testing
First Name
Last Name
Previous
Next
Submit
Press
Enter
2
Site
Previous
Next
Submit
Press
Enter
3
Date
-
Date
Year
Month
Day
Previous
Next
Submit
Press
Enter
4
Testing to be completed on this visit
Monthly
6 Monthly
Yearly
5 Yearly
Fire Alarm
Yes
No
N/A
Yes
No
N/A
Row 0, Column 0
Yes
No
N/A
Yes
No
N/A
Row 0, Column 1
Yes
No
N/A
Yes
No
N/A
Row 0, Column 2
Yes
No
N/A
Yes
No
N/A
Row 0, Column 3
Fire Extinguishers
Yes
No
N/A
Yes
No
N/A
Row 1, Column 0
Yes
No
N/A
Yes
No
N/A
Row 1, Column 1
Yes
No
N/A
Yes
No
N/A
Row 1, Column 2
Yes
No
N/A
Yes
No
N/A
Row 1, Column 3
Fire Sprinklers
Yes
No
N/A
Yes
No
N/A
Row 2, Column 0
Yes
No
N/A
Yes
No
N/A
Row 2, Column 1
Yes
No
N/A
Yes
No
N/A
Row 2, Column 2
Yes
No
N/A
Yes
No
N/A
Row 2, Column 3
Hydrants
Yes
No
N/A
Yes
No
N/A
Row 3, Column 0
Yes
No
N/A
Yes
No
N/A
Row 3, Column 1
Yes
No
N/A
Yes
No
N/A
Row 3, Column 2
Yes
No
N/A
Yes
No
N/A
Row 3, Column 3
Pumps
Yes
No
N/A
Yes
No
N/A
Row 4, Column 0
Yes
No
N/A
Yes
No
N/A
Row 4, Column 1
Yes
No
N/A
Yes
No
N/A
Row 4, Column 2
Yes
No
N/A
Yes
No
N/A
Row 4, Column 3
Fire Hose Reels
Yes
No
N/A
Yes
No
N/A
Row 5, Column 0
Yes
No
N/A
Yes
No
N/A
Row 5, Column 1
Yes
No
N/A
Yes
No
N/A
Row 5, Column 2
Yes
No
N/A
Yes
No
N/A
Row 5, Column 3
Gas System
Yes
No
N/A
Yes
No
N/A
Row 6, Column 0
Yes
No
N/A
Yes
No
N/A
Row 6, Column 1
Yes
No
N/A
Yes
No
N/A
Row 6, Column 2
Yes
No
N/A
Yes
No
N/A
Row 6, Column 3
Fire Alarm
Fire Extinguishers
Fire Sprinklers
Hydrants
Pumps
Fire Hose Reels
Gas System
Monthly
Yes
No
N/A
Yes
No
N/A
Row 0, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 0, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 0, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 0, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 1, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 1, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 1, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 1, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 2, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 2, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 2, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 2, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 3, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 3, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 3, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 3, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 4, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 4, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 4, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 4, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 5, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 5, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 5, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 5, Column 3
Monthly
Yes
No
N/A
Yes
No
N/A
Row 6, Column 0
6 Monthly
Yes
No
N/A
Yes
No
N/A
Row 6, Column 1
Yearly
Yes
No
N/A
Yes
No
N/A
Row 6, Column 2
5 Yearly
Yes
No
N/A
Yes
No
N/A
Row 6, Column 3
1
of 7
Previous
Next
Submit
Press
Enter
5
3.1 Monthly Service 7 6 Monthly Service
Complete all monthly & 6 monthly tests
Previous
Next
Submit
Press
Enter
6
3.2 Hydrant Valves Above & Below Ground
NOTE: To prevent water damage, it is recommended that a suitable adapter to limit water flow be used for this test on internal hydrants. Each hydrant in the system should be opened separately..
Previous
Next
Submit
Press
Enter
7
3.3 Hydrant Water Supply
(c) TEST each valve monitor (where fitted) by closing and re-opening the valve. Verify correct indication at the CIE.
Previous
Next
Submit
Press
Enter
8
3.4 Non Return Valves
VERIFY that all non-return valves are operating freely and are seating correctly.
Previous
Next
Submit
Press
Enter
9
3.5 Hydrant Hose Where Fitted
VERIFY all branch pipe, nozzles and hose couplings waterways are unobstructed and in good condition.
Previous
Next
Submit
Press
Enter
10
3.6 Pressure Reducing Station Test
(a) OPERATE all pressure-reducing valves and verify correct operation under flow conditions. (b) VERIFY that pressure readings on the low pressure side of the valves are within the range stated at the pressure-reducing valve station. ………….kPa (c) OPERATE pressure-relief valve and record operating pressure. If necessary, adjust the setting to relieve at 50 kPa above the operating pressure of the pressure-reducing valve. Replace the tamper seal if necessary. NOTE: The pressure-relief valve test may be carried out using a portable test apparatus.
Previous
Next
Submit
Press
Enter
11
3.7 Water Supply Proving Test
CONDUCT a water supply proving test for each water supply verifying that the system flow and pressure requirements meet the design criteria, using either— (a) a fixed flow meter test facility; or Static supply pressure ……...…..kPa Flowing pressure ………….kPa (b) a portable test apparatus at the most hydraulically disadvantaged hydrant valve(s). Flow L/s……………. ………….kPa No. hydrants flowing……….. NOTES: 1 Where the water supply is the sole source of water for both sprinkler and hydrant systems, both sprinkler and hydrant demands should be available simultaneously. 2 In high-rise buildings where there are multiple pressure zones, a water supply proving test should be carried out on the most remote hydrant in each zone.
Previous
Next
Submit
Press
Enter
12
3.8 Hydrant System Interface Test
(a) CONDUCT a functional system test via the pressure switch or flow switch with other interfaced fire systems. (b) VERIFY that the interface functions in accordance with the building systems interface schematic. NOTE: It is recommended that the responsible entity coordinate testing the interfaced fire protection systems.
Previous
Next
Submit
Press
Enter
13
3.9 Water Supply Tank Atmospheric
Perform routine service in accordance with Section 5.
Previous
Next
Submit
Press
Enter
14
3.10 Water Supply River, Lake Etc Strainers/Screens
(a) CHECK suction inlet strainer(s) or screen(s). (b) Following water supply proving test (Table 4.4.2 Item 2.6), CLEAN suction inlet strainer(s). Lower raised screen and raise and clean ‘in-use’ screen.
Previous
Next
Submit
Press
Enter
15
3.11 Survey - Installation
(a) Pipework—CHECK that exposed water distribution system, including pipework, pipe supports and valve, appears free from corrosion and damage, not subject to external loads and pipework is properly supported. (b) Hydrant obstructions—CHECK for obstructions likely to impede hydrant valve access.
Previous
Next
Submit
Press
Enter
16
3.12 Survey Design
(a) Occupancy—CHECK that hydrant design remains applicable for current building arrangement or use. (b) Site documentation—CHECK that block plans, emergency instructions and pressure schedules contain the details required in accordance with AS 2419.1.
Previous
Next
Submit
Press
Enter
17
Test Results of devices
Previous
Next
Submit
Press
Enter
18
Testing comments/Suggestions/Defects
Huge
Large
Normal
Small
Ok
quote
Created with Sketch.
Ok
Previous
Next
Submit
Press
Enter
19
Testing comments/Suggestions/Defects Photos
Drag and drop files here
Select files to upload
Max. file size
: 10.6MB
Browse Files
Cancel
of
Previous
Next
Submit
Press
Enter
20
Signature
Clear
Previous
Next
Submit
Press
Enter
Should be Empty:
Question Label
1
of
20
See All
Go Back
Submit