You can always press Enter⏎ to continue
AS1670.1-2018 Commissioning
START
1
Project
N/APrevious
Next
Submit
Press
Enter
2
Technician
First Name
Last Name
N/APrevious
Next
Submit
Press
Enter
3
Date
-
Date
Day
Month
Year
N/APrevious
Next
Submit
Press
Enter
4
Details
Area/level
AS1670.1-2004
AS1670.1-2015
AS1670.1-2018
AS1670.1-2004
AS1670.1-2015
AS1670.1-2018
Australian Standards
Please Select
Fire detection system
Fire alarm cabling
Occupant warning cabling
Network cabling
Please Select
Please Select
Fire detection system
Fire alarm cabling
Occupant warning cabling
Network cabling
What service is getting tested
N/APrevious
Next
Submit
Press
Enter
5
A.3 a - Equipment
Check that all equipment
is listed in the table of system components;
meets the referenced component Standard;
has been located, installed and interconnected in accordance with the system design documentation and the requirements of this Standard; and
is installed in an environment for which they are suitable.
N/A
N/APrevious
Next
Submit
Press
Enter
6
A.3 b - Detectors
Check that all detectors and other devices used in the system are
compatible with the relevant parts of FDCIE; particularly ensure that the allowed number of detectors and other devices for each transmission path are not exceeded;
not set to a sensitivity outside that prescribed in the referenced component Standard;
in accordance with the requirements of Clause 3.11 (where CO fire detectors are incorporated in the system); and
are activated when tested and correctly indicate on the detectors and at the FDCIE.
N/A
N/APrevious
Next
Submit
Press
Enter
7
A.3 c - Networked FDCIE
Check that the requirements of Clause 2.4 are met.
N/A
N/APrevious
Next
Submit
Press
Enter
8
A.3 d - Distributed parts of CIE
Check that the requirements of Clause 2.4 are met.
N/A
N/APrevious
Next
Submit
Press
Enter
9
A.3 e - Zone block diagram
Check the zone block plan is adjacent to the FBP and reflects the correct detection zone layout as defined in the design documentation.
N/A
N/APrevious
Next
Submit
Press
Enter
10
A.3 f - Mains Power
the mains power for the system is connected in accordance with AS/NZS 3000;
the isolating switch disconnects all active conductors;
the five operations of the mains isolating switch do not cause an alarm to be indicated on the system; and
a fault is indicated within 90 min of mains power being removed.
N/A
N/APrevious
Next
Submit
Press
Enter
11
A.3 g - Standby Power Source
the standby power source is of a suitable type and capacity in accordance with the requirements of Clause 3.15.5 and the design documentation;
the float voltage, charger type and setting is correct and in accordance with the battery specifications and design requirements; and
the date of battery manufacture is recorded.
a fault is indicated within 90 min of mains power being removed.
N/A
N/APrevious
Next
Submit
Press
Enter
12
A.3 h - Battery temperature and voltage
Allow the system to operate in the quiescent state for a period of not less than 24 h. At the end of this period measure the temperature of the battery space. Check that the battery voltage corresponds to that specified by the battery documentation for the measured temperature.
N/A
N/APrevious
Next
Submit
Press
Enter
13
A.3 i - Cabling
NOTE This may be done through a random inspection of each type of wiring system specified in the design documentation or required by this Standard including fire rating requirements.
Check that the cabling is in accordance with Clause 3.24.
N/A
N/APrevious
Next
Submit
Press
Enter
14
A.3 j - Detection zone limitations
Check that the detection zone limitations in Clause 2.3 are not exceeded.
N/A
N/APrevious
Next
Submit
Press
Enter
15
A.3 k - Detection zone parameters
Check that actuating devices using radio transmission paths meet the requirements of the referenced Standards in Clause 1.3, including that the receiver responds to alarm, tamper, low standby power signals and gives a fault signal when the supervisory signal condition is absent.
N/A
N/APrevious
Next
Submit
Press
Enter
16
A.3 l - Radio Transmission Paths
Measure and verify that detection zone transmission path parameters specified in the FDCIE specification are met.
N/A
N/APrevious
Next
Submit
Press
Enter
17
A.3 m - Operation of fault and alarm signals
Conduct an appropriate test on each detection zone transmission path and check that fault and fire alarm signals are correctly detected and indicated as the correct detection zone. Also check that other required indicators and relevant outputs of the FDCIE operates as intended.
N/A
N/APrevious
Next
Submit
Press
Enter
18
A.3 n - Transmission path isolators (TPI)
Check the operation of short-circuit isolation for each detection zone.
N/A
N/APrevious
Next
Submit
Press
Enter
19
A.3 o - Transmission path isolators (TPI)
Check that transmission paths are protected in accordance with Clause 3.26 and upgraded where required by the system design documentation.
N/A
N/APrevious
Next
Submit
Press
Enter
20
A.3 p - Alarm Mimic panel
Check the correct operation of all alarm mimic panels, annunciators, and the like.
N/A
N/APrevious
Next
Submit
Press
Enter
21
A.3 q - Detection zone controls
Operate the controls provided for each detection zone to check for correct operation.
N/A
N/APrevious
Next
Submit
Press
Enter
22
A.3 r - Alarm verification facility (AVF)
Check that the AVF has been implemented correctly, in accordance with Clause 3.2.5.
N/A
N/APrevious
Next
Submit
Press
Enter
23
A.3 s - FDCIE response to fire detection device operation
Check that each device, detector or sensor operates when tested with a medium suitable for the device type and that the alarm has indicated on the correct detection zone at the FDCIE and, if applicable, at the tested device.
N/A
N/APrevious
Next
Submit
Press
Enter
24
A.3 t - Fault response time
Test each detection zone transmission path and check that the response to a fault is indicated on the FDCIE in not less than 100 s.
N/A
N/APrevious
Next
Submit
Press
Enter
25
A.3 u - Alarm response time
Test at least one detector in each detection zone transmission path and check that the response to the alarm is indicated on the FDCIE in not less than 10s or the period specified when dependency on more than one alarm signal is used.
N/A
N/APrevious
Next
Submit
Press
Enter
26
A.3 v - Supervisory signal response time
Test at least one supervisory device in each detection transmission path and check that the response to the supervisory device is indicated on the FDCIE in not less than 100 s.
N/A
N/APrevious
Next
Submit
Press
Enter
27
A.3 w - Alarm acknowledgement facility (AAF)
Check that any alarm acknowledgement facility operates correctly, in accordance with Clause 3.2.2.
N/A
N/APrevious
Next
Submit
Press
Enter
28
A.3 x - Alarm delay facility (ADF)
Check that any alarm delay operates correctly, in accordance with Clause 3.2.3.
N/A
N/APrevious
Next
Submit
Press
Enter
29
A.3 y - Alarm investigation facility (AIF)
Check that any alarm delay operates correctly, in accordance with Clause 3.2.4.
N/A
N/APrevious
Next
Submit
Press
Enter
30
A.3 z - Occupant warning system:
Check that output to the building occupant warning system at the FDCIE operates within 3s of the fire alarm condition and that the occupant warning system operates within the time specified with the requirements of AS 4428.16 orAS ISO 7240.3 as applicable.
Check the sound pressure level meets the requirements of Clause 3.22 in each occupied space.
Record on the "as-installed" drawings the SPL achieved for the reference location of each loudspeaker transmission path.
N/A
N/APrevious
Next
Submit
Press
Enter
31
A.3 aa - External alarm indication
Check that the external alarm indication is visible from the main approach to the building and is adjacent to the designated building entry point.
N/A
N/APrevious
Next
Submit
Press
Enter
32
A.3 bb - Designated site entry point
Check that each building can be identified from the DSEP by at least one of the means specified in Clause 2.2.2.
N/A
N/APrevious
Next
Submit
Press
Enter
33
A.3 cc - Manual call points
the correct operation of each MCP;
that the activation of MCP on the same transmission path as other detection devices does not cause existing detector alarm indications to be extinguished, and
that MCPs are not subject to alarm dependency.
N/A
N/APrevious
Next
Submit
Press
Enter
34
A.3 dd - Smoke and fire door release
Check the operation of each device.
N/A
N/APrevious
Next
Submit
Press
Enter
35
A.3 ee - Suppression system
Check that each suppression system flow/pressure switch is connected to the FDCIE as a separate detection zone.
N/A
N/APrevious
Next
Submit
Press
Enter
36
A.3 ff- Flame detectors
the number and tvpe of detectors provide adequate protection of the area;
there are no "blind" spots in areas protected;
detectors are rigidly fixed;
detector lenses are clean and adequately protected from dust and extraneous radiation sources; and
the detector responds to a flame source or simulated flame.
N/A
N/APrevious
Next
Submit
Press
Enter
37
A.3 gg - Aspirating smoke detectors
Measure and record the transport time (TT) from the most disadvantaged sampling point for each sampling pipe or branch.
Visually inspect every sampling point to ensure it is not obstructed.
Check the response of all capillary sampling points using a test medium placed at each sampling point.
detectors are rigidly fixed;
detector lenses are clean and adequately protected from dust and extraneous radiation sources; and
Check the operation of all alarm threshold settings and indicators using a test medium on at least one sampling point as follows:
The operation of remote indication of alarm and fault signals.
The operation of airflow failure indicators.
The operation of the system (signal) failure indicators.
The isolate and reset functions.
The fault and alarm test facilities.
N/A
N/APrevious
Next
Submit
Press
Enter
38
A.3 hh - Duct sampling smoke detectors
Measure and record the transport time (TT) from the most disadvantaged sampling point for each sampling pipe or branch.
the alarm indicator is clearly visible from a trafficable area;
the duct air velocity exceeds the minimum velocity specified for the unit; and
if the velocity does not exceed the minimum specified for the unit, the measured differential pressure is at least the minimum specified for the unit.
N/A
N/APrevious
Next
Submit
Press
Enter
39
A.3 ii - Connectable device control functions
Test each connectable device by operating the detection zone facility or facilities associated with the connectable device and check for the correct operation of the connectable devices.
N/A
N/APrevious
Next
Submit
Press
Enter
40
A.3 jj - Detection zone descriptions
Check that all detection zones have been correctly labelled and that the detection zone is immediately apparent from the labelling or correctly described on an alphanumeric display.
N/A
N/APrevious
Next
Submit
Press
Enter
41
A.3 kk - Cause and effect matrix
Check the overall svstem performance is as specified in the cause and effect matrix.
Not supplied at FIP
N/A
N/APrevious
Next
Submit
Press
Enter
42
A.3 ll - Systems interface testing
Prior to any interface testing, check that all systems listed in the system interface schedule are complete and operable. This will involve checking that all systems interfaces to the FDAS [e.g. BMCS, motor control centres (smoke control), security system (door release), nurse call systems, lifts, automatic doors, sprinklers, gaseous extinguishing systems, safety services and other ancillary control functions] are correctly connected. NOTE The "end-to-end" test should include the activation of associated detection devices to confirm that all required functions operate correctly in accordance with the system interface matrix.
The systems interface tests should confirm
the automatic "end-to-end" operation of all interfaced svstems:
the correct indication of operation on the FBP, FDCIE, FFCP, EWCIE, EICIE, FFCP or SHCIE as applicable.
N/A
Other
N/APrevious
Next
Submit
Press
Enter
43
Testing notes
Huge
Large
Normal
Small
Ok
quote
Created with Sketch.
Ok
N/APrevious
Next
Submit
Press
Enter
44
IFPS Signature
Clear
N/APrevious
Next
Submit
Press
Enter
45
Client Signature if Applicable
Clear
N/APrevious
Next
Submit
Press
Enter
Should be Empty:
Question Label
1
of
45
See All
Go Back
Submit