  • Outdoor Unit:

  •  
  • Outdoor Unit:

  •  
  • If voltages are not within range. shut power off to the outdoor unit. Remove wires for each zone and recheck voltages at outdoor terminal strips.

  •  
  • Image-148
  • Diagnostic Instructions:                                                                                                                           Run all the units in heat or cool with the fan speed set to high. Set the controller as high or low as possible for the mode you are in. Wait 20 minutes then record the following information.

  • Indoor Unit A

  •  
  • Indoor Unit B

  •  
  • Indoor Unit C

  •  
  • Indoor Unit D

  •  
  • Image-149
  • Refrigerant:                                                                                                        

         Multi head systems are susceptible to cross piping and wiring. Always cycle one head on at a time and check the TD across the indoor coil. If TD is normal then wiring and piping are correct, if not trace wiring and piping for each zone and correct.

         Typical Super heat for the indoor unit in cooling mode with more than a 5degree deviation from set point with the fan speed set to high is between 2-5 degrees F

         Typical Sub-Cooling for the indoor unit in heating mode with more than a 5degree deviation from set point with the fan speed set to high is between 5-9 degrees F

         Max Pressure Drop on the indoor unit and piping is 50 Psi

         Max Psi drop between the discharge Psi and Saturated liquid line in A/C mode 150 Psi                                                                

  • Electrical:


    Check line voltage at the outdoor unit (L1-L2) and voltage being supplied to each indoor unit at S1, S2 & S3. Readings should be as followed:
         L1 – L2 = 208/240 Volts A/C
         S1 - S2 = 208/240 Volts A/C
         S1 – S3 Should be the same as S1 – S2
         S2 –S3(wires connected) = Pulsating D/C Voltage
         S2 –S3(wires disconnected) = 24 -29 D/C Volts steady
         S2 – S3 = 80 – 120 VDC S1 and S2 are Swapped
         DC Bus Voltage = 1.414 x input voltage
         M-Net Voltage 28-30Vdc


    Do Not remove any wires until the DC Bus voltage is below 17 VDC

  • Controls:


    -The return thermistor has a built in heat off set of 7 degrees F when the system is in the heating mode
    - MVZ air handlers that use the KUMO Control should use a remote temperature sensor to sense room
    temperature

  • Image-150
  • Image-65
  • Image-78
  •  
  • Should be Empty: