EV Charger Maintenance
Site Name/Address
*
Number Of Chargers
*
Please Select
1
2
3
Charger 1
Manufacturer
*
Serial Number
*
Supply Characteristics
*
Cable Size
*
Source Of Supply
*
Browse Files
Drag and drop files here
Choose a file
Cancel
of
Charger Identification
Charger brand & model
*
Charger serial number
*
Connector type(s) (e.g. Type 2, CCS)
*
Rated output (kW)
*
Supply type (1-phase / 3-phase)
*
Installation date
*
Last service date
*
Visual Inspection
No Visible Damage or Wear
*
Pass
Fail
Securely Mounted
*
Pass
Fail
Clean & free of obstruction
*
Pass
Fail
N/A
Charging socket condition
*
Pass
Fail
N/A
Tethered lead condition
*
Pass
Fail
N/A
Signage present and legible
*
Pass
Fail
N/A
Isolation switch accessible
*
Pass
Fail
N/A
Earth rod present (if TT)
*
Pass
Fail
N/A
Surge protection device present (if required)
*
Pass
Fail
N/A
Functional testing
Charger Powers Up Correctly
*
Pass
Fail
N/A
status Light Normal
*
Pass
Fail
N/A
RFID / keypad working
*
Pass
Fail
N/A
Communication with backend / app confirmed (if smart)
*
Pass
Fail
N/A
Locking mechanism (if present) functional
*
Pass
Fail
N/A
Load management or CT clamp connected and operational
*
Pass
Fail
N/A
Dead tests
Continuity of protective conductors, including main earthing conductor, and main and supplementary protective bonding conductors
*
Yes
No
N/A
Continuity of ring final circuit conductors
*
Yes
No
N/A
Insulation Resistance
*
L-L >500MΩ Pass
L-L >500MΩ Fail
L-E >500MΩ Pass
L-E >500MΩ Fail
Protection by SELV, PELV or electrical separation
*
Yes
No
N/A
Polarity
*
Yes
No
Live Testing
RCD AC 1/2x @ 0°
*
RCD AC 1/2x @ 180°
*
RCD AC 1x @ 0°
*
RCD AC 1x @ 180°
*
RCD AC 5x @ 0°
*
RCD AC 5x @ 180°
*
RCD DC 1x @ 0°
*
RCD DC 1x @ 180°
*
Measured maximum earth fault loop impedance (Zs)
*
Is Zs within maximum permitted earth fault loop impedance for circuit
*
Yes
No
Perspective Fault Current (PFC)
*
Voltage
*
PEN Fault Detection Test
*
Pass
Fail
N/A
Type option 4
Site Specific Checks
Safe access around unit
*
Pass
Fail
Cable management (trip hazard prevention)
*
Pass
Fail
N/A
Cable storage facility secure
*
Pass
Fail
N/A
Lighting for evening use
*
Pass
Fail
N/A
Maintenance Actions Taken
Cleaned unit
*
Yes
No
N/A
Firmware updated
*
Yes
No
N/A
Faults cleared
*
Yes
No
N/A
Recommendations made
Charging Point Photos x3
*
Browse Files
Drag and drop files here
Choose a file
Cancel
of
Outcome
*
Pass
Fail
Recommended next Inspection
*
3 Months
6 Months
12 Months
Recommended Remedial Actions
Date
*
-
Day
-
Month
Year
Date
Name of engineer completing charger maintenance
*
First Name
Last Name
Signature
*
Charger 2
Manufacturer
*
Serial Number
*
Supply Characteristics
*
Cable Size
*
Source Of Supply
*
Browse Files
Drag and drop files here
Choose a file
Cancel
of
Charger Identification
Charger brand & model
*
Charger serial number
*
Connector type(s) (e.g. Type 2, CCS)
*
Rated output (kW)
*
Supply type (1-phase / 3-phase)
*
Installation date
*
Last service date
*
Visual Inspection
No Visible Damage or Wear
*
Pass
Fail
Securely Mounted
*
Pass
Fail
Clean & free of obstruction
*
Pass
Fail
N/A
Charging socket condition
*
Pass
Fail
N/A
Tethered lead condition
*
Pass
Fail
N/A
Signage present and legible
*
Pass
Fail
N/A
Isolation switch accessible
*
Pass
Fail
N/A
Earth rod present (if TT)
*
Pass
Fail
N/A
Surge protection device present (if required)
*
Pass
Fail
N/A
Functional testing
Charger Powers Up Correctly
*
Pass
Fail
N/A
status Light Normal
*
Pass
Fail
N/A
RFID / keypad working
*
Pass
Fail
N/A
Communication with backend / app confirmed (if smart)
*
Pass
Fail
N/A
Locking mechanism (if present) functional
*
Pass
Fail
N/A
Load management or CT clamp connected and operational
*
Pass
Fail
N/A
Dead tests
Continuity of protective conductors, including main earthing conductor, and main and supplementary protective bonding conductors
*
Yes
No
N/A
Continuity of ring final circuit conductors
*
Yes
No
N/A
Insulation Resistance
*
L-L >500MΩ Pass
L-L >500MΩ Fail
L-E >500MΩ Pass
L-E >500MΩ Fail
Protection by SELV, PELV or electrical separation
*
Yes
No
N/A
Polarity
*
Yes
No
Live Testing
RCD AC 1/2x @ 0°
*
RCD AC 1/2x @ 180°
*
RCD AC 1x @ 0°
*
RCD AC 1x @ 180°
*
RCD AC 5x @ 0°
*
RCD AC 5x @ 180°
*
RCD DC 1x @ 0°
*
RCD DC 1x @ 180°
*
Measured maximum earth fault loop impedance (Zs)
*
Is Zs within maximum permitted earth fault loop impedance for circuit
*
Yes
No
Perspective Fault Current (PFC)
*
Voltage
*
PEN Fault Detection Test
*
Pass
Fail
N/A
Type option 4
Site Specific Checks
Safe access around unit
*
Pass
Fail
Cable management (trip hazard prevention)
*
Pass
Fail
N/A
Cable storage facility secure
*
Pass
Fail
N/A
Lighting for evening use
*
Pass
Fail
N/A
Maintenance Actions Taken
Cleaned unit
*
Yes
No
N/A
Firmware updated
*
Yes
No
N/A
Faults cleared
*
Yes
No
N/A
Recommendations made
Charging Point Photos x3
*
Browse Files
Drag and drop files here
Choose a file
Cancel
of
Outcome
*
Pass
Fail
Recommended next Inspection
*
3 Months
6 Months
12 Months
Recommended Remedial Actions
Date
*
-
Day
-
Month
Year
Date
Name of engineer completing charger maintenance
*
First Name
Last Name
Signature
*
Charger 3
Manufacturer
*
Serial Number
*
Supply Characteristics
*
Cable Size
*
Source Of Supply
*
Browse Files
Drag and drop files here
Choose a file
Cancel
of
Charger Identification
Charger brand & model
*
Charger serial number
*
Connector type(s) (e.g. Type 2, CCS)
*
Rated output (kW)
*
Supply type (1-phase / 3-phase)
*
Installation date
*
Last service date
*
Visual Inspection
No Visible Damage or Wear
*
Pass
Fail
Securely Mounted
*
Pass
Fail
Clean & free of obstruction
*
Pass
Fail
N/A
Charging socket condition
*
Pass
Fail
N/A
Tethered lead condition
*
Pass
Fail
N/A
Signage present and legible
*
Pass
Fail
N/A
Isolation switch accessible
*
Pass
Fail
N/A
Earth rod present (if TT)
*
Pass
Fail
N/A
Surge protection device present (if required)
*
Pass
Fail
N/A
Functional testing
Charger Powers Up Correctly
*
Pass
Fail
N/A
status Light Normal
*
Pass
Fail
N/A
RFID / keypad working
*
Pass
Fail
N/A
Communication with backend / app confirmed (if smart)
*
Pass
Fail
N/A
Locking mechanism (if present) functional
*
Pass
Fail
N/A
Load management or CT clamp connected and operational
*
Pass
Fail
N/A
Dead tests
Continuity of protective conductors, including main earthing conductor, and main and supplementary protective bonding conductors
*
Yes
No
N/A
Continuity of ring final circuit conductors
*
Yes
No
N/A
Insulation Resistance
*
L-L >500MΩ Pass
L-L >500MΩ Fail
L-E >500MΩ Pass
L-E >500MΩ Fail
Protection by SELV, PELV or electrical separation
*
Yes
No
N/A
Polarity
*
Yes
No
Live Testing
RCD AC 1/2x @ 0°
*
RCD AC 1/2x @ 180°
*
RCD AC 1x @ 0°
*
RCD AC 1x @ 180°
*
RCD AC 5x @ 0°
*
RCD AC 5x @ 180°
*
RCD DC 1x @ 0°
*
RCD DC 1x @ 180°
*
Measured maximum earth fault loop impedance (Zs)
*
Is Zs within maximum permitted earth fault loop impedance for circuit
*
Yes
No
Perspective Fault Current (PFC)
*
Voltage
*
PEN Fault Detection Test
*
Pass
Fail
N/A
Type option 4
Site Specific Checks
Safe access around unit
*
Pass
Fail
Cable management (trip hazard prevention)
*
Pass
Fail
N/A
Cable storage facility secure
*
Pass
Fail
N/A
Lighting for evening use
*
Pass
Fail
N/A
Maintenance Actions Taken
Cleaned unit
*
Yes
No
N/A
Firmware updated
*
Yes
No
N/A
Faults cleared
*
Yes
No
N/A
Recommendations made
Charging Point Photos x3
*
Browse Files
Drag and drop files here
Choose a file
Cancel
of
Outcome
*
Pass
Fail
Recommended next Inspection
*
3 Months
6 Months
12 Months
Recommended Remedial Actions
Date
*
-
Day
-
Month
Year
Date
Name of engineer completing charger maintenance
*
First Name
Last Name
Signature
*
Continue
Continue