• Commissioning and Start Up Form

    Chiller Start Up Procedure Form Doc. N°061103
  • To enable warranty this form must be filled out.

    The warranty starts on the date of initial startup if startup or 30 days after delivery whichever occurs first.

    Refer to unit installation and user manual.

  • Commission Date:*
     - -
  • Check all that apply:
  • Unit Information

    • OPEN SECTION 1 
    • Unit #1

    • Unit #2

    • Unit #3

    • Unit #4

    • Unit #5

    • Unit #6

    • Unit #7

    • Unit #8

    • Unit #9

    • Unit #10

    • OPEN SECTION 1 
    • 1. Preliminary Operation

    • WARNING: The following operation must be done without the power supply (unit with the main switch in the OFF position).

      WARNING: Before the following operations, disconnect the unit from the power supply. The main switch must be in the OFF position. Please check with a voltmeter on each phase in order to be sure of the absence of voltage. Apply a label to the unit if required by the safety procedure of the country.

    • 1.2. Ground connection (Earthing): Check the connection to the ground and test it. (see the Technical Manual). Check each unit individually.

    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • The following operation must be done with the power supply connected. The unit must not be switched ON until check 1.4 has been made.

    • 2. Hydraulic Circuit

    • 2.2. Filter: Check a mechanical filter is installed at the entry of the evaporator. (compulsory; if the mechanical filter is not installed any warranty is immediately voided). Check each unit individually.

    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Select metric:*
    • Select metric:*
    • Select metric:*
    • Select metric:*
    • 2.7. Flow Switch: Check and verify the correct functioning of the flow switch. Closing the water valve of the hydraulic circuit slowly, you should cause an Alarm that will be shown on the unit display. Once this check has been done please open the valve again and reset the alarm. (compulsory; if the mechanical filter is not installed any warranty is immediately voided). Check each unit individually.

    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • 3. Start Up

    • 3.1. Start up the unit: Once all the above checks have been done it is possible to start up the unit pressing the ON button. Check each unit individually.

    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Select metric:*
    • Select metric:*
    • Regulation:*
    • 3.4. Input current: Check the fans and compressor input current and verify it with the technical data. Check each unit individually.

    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Unit #1

    • Unit #2

    • Unit #3

    • Unit #4

    • Unit #5

    • Unit #6

    • Unit #7

    • Unit #8

    • Unit #9

    • Unit #10

    • 4. Refrigeration Circuit

    • Select metric:*
    • Select metric:*
    • Select metric:*
    • 4.4. Superheat: Check and verify that the refrigerant superheat is between 4 and 8°C. This operation to be done comparing the temperature measured with a contact thermometer located on the compressor suction, with the temperature shown in the manometer (if not present on the unit you need to install one for the check) set on the suction side (the saturated temperature corresponding to the suction pressure). The difference between the two values gives the superheat value). Check each unit individually.

    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Notes for Parameter 4.5:
    • 4.5. Subcooling: Check and verify that the refrigerant subcooling is between 4 and 6°C. This operation can be done comparing the temperature measured with a contact thermometer located on the outlet pipe of condenser, with the temperature shown in the manometer (if not present on the unit you need to install one for the check) set on the outlet of the condenser (saturated temperature corresponding to the condenser outlet pressure). The difference between the two values gives the subcooling value). Check each unit individually.

    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Notes for Parameter 4.6:
    • 4.6. Discharge Temperature: Check the Discharge Temperature of the compressor. If the subcooling and the superheat values are correct the temperature measured at the discharge line of the compressor must be 30 to 40°C above the condensing temperature. Check each unit individually.

    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • Checked each of the following units:
    • 5. Safety and Control Devices

    • Select metric:
  • Pictures

    If necessary, upload pictures of the unit, name plate, etc.