Notes:
1) All service equipment disconnecting means shall be installed with in a distance of 8 circuit feet from service entrance.
2) All services rated above a 320 amp meter base will be required to have an outside main disconnect.
3) If the service is CT'd on pole or pad mount transformer, then customer will install secondary service wire and conduit.
4) If service is CT'd on pole, then customer will install 90 degree long sweeping elbows at pole.
5) If service is CT'd on pad mount transformer, then HILCO will install 90 degree long sweeping elbows and install pad for the transformer.
6) A transocket can be used if there will be multiple tenants or refer to spec sheet for main disconnect and multiple meter installation examples.
7) HILCO will install secondary wire and conduit for all services rated at 320 amps or less and all transocket installations.